• About Dreisilker
  • Career Opportunities
  • Our Blog
  • Contact Us
  • Request a Quote
Call Dreisilker @ 630-469-7510
Dreisilker Electric Motors
  • Shop Online
  • Branch Locations
    • Illinois
      • Alsip
      • Chicago
      • Crystal Lake
      • Elk Grove Village
      • Glen Ellyn
    • Georgia
      • Marietta
    • Texas
      • Carrollton
  • Repair Services
    • Repair by Type
      • AC Motors
      • Blower Motors
      • Centrifugal Blower Motor Repair
      • Chiller Motor Repair
      • Compressor Motors
      • DC Motors
      • Foreign Motors
      • Gas Booster Repair
      • Gearboxes
      • Gear Motor Repair
      • Generators
      • Printing Press Motor Repair
      • Pumps
      • Servo Motors
      • UL Explosion Proof Motors
      • Vacuum Pumps
      • Wind Turbines
    • Repair Services
      • MotorSafe Repair Process
      • Advanced Varnishing
      • Commutator Repair
      • Machining Services
      • Rewinding Services
        • Armature Repair
        • Armature Rewinding
    • Repair by Industry
      • Heat Treating
      • Crane & Hoist
      • Manufacturing
      • Machine Tool
      • Printing
      • Plastics
      • Steel Mill
  • Field Services
    • Field Services
      • Dynamic Balancing
      • Electronics Repair
      • Infrared Inspection
      • Laser Shaft Alignment
      • Motor and Electronics Troubleshooting
      • Electric Motor Diagnostic Tests
      • Variable Frequency Drive Support
      • Vibration Analysis
    • Engineering Services
      • Electric Motor Contract Manufacturing
      • Complete Machine Shop
      • Balloon and Solid Shaft Repair
  • Motor and Drive Sales
    • All Brands
      • Century Electric Motors
      • CoolBLUE Inductive Absorbers
      • Fasco
      • Genteq
      • Lau
      • Leeson
      • Marathon Electric
      • Optibelt
      • Packard Electric Motors
      • Siemens
      • Yaskawa VFD
      • Teco Westinghouse

How-To Wire Condenser Fan Motors Properly in 3-Wire & 4-Wire Configurations

May 24, 2018/12 Comments/in Condenser, Cooling Season /by Lynn Dreisilker

“My original condenser fan motor has three wires and the replacement condenser fan motor that I bought has four wires – did I buy the wrong motor?”

This is by far the most common post-transaction question that we receive from customers that have recently purchased replacement condenser fan motors. Simply put, no – you did not buy the wrong condenser fan motor. While most original condenser fan motors only have three wires, it’s very common for replacement condenser fan motors to have four. This guide will explain how to wire your new condenser fan motor using a four wire setup or a three wire setup when using a single run capacitor or a dual run capacitor.

A review of the components:

If you recall from our residential cooling season guide, outdoor condenser units use a switch called a contactor. This switch is controlled by the thermostat and closes to complete an electrical circuit when electricity needs to be supplied to your condenser fan motor and compressor. Think of the contactor almost as a gatekeeper – two legs of 115 volt electric supply need to flow through it in order for your system to function properly.

Condenser units also use a component called a run capacitor. Run capacitors allow condenser fan motors and compressors to run more efficiently and they’re rated by a unit of measurement called microfarad. Dual run capacitors are used for both your condenser fan motor and your compressor. Single run capacitors are used exclusively for just your condenser fan motor or just your compressor. Like your contactor, your capacitor needs to be wired correctly in order for it to function properly.

Run and Start Capacitors

 

Using a dual run capacitor:

If you’re using a dual run capacitor, you’re only going to use three of the four leads coming off the new condenser fan motor.

You’re going to wire the black lead to where the black lead on your previous condenser fan motor was wired to. This will likely be back to your contactor. You’re going to wire the white lead to where the white lead on your previous condenser fan motor was wired to. This will likely be the “C” or “Common” terminal on your dual run capacitor. Finally, you’re going to wire the brown lead to where your previous brown lead was wired to. This will likely be the “F” or “Fan” terminal on your dual run capacitor. The brown lead with the white tracer will not be used for this setup. You can use a wire nut and electrical tape to tie it off.

NOTE: You’ll need a jumper between the “C” or “Common” terminal on the capacitor and one leg of the contactor.

Using a single run capacitor with a four wire setup:

If you purchased a new condenser fan motor with a new single run capacitor, this will be the wiring setup that you’ll be using. You’re going to wire the black lead to where the black lead on your previous condenser fan motor was wired to. This will likely be back to your contactor. You’re going to wire the white lead back to the other leg of your contactor. You’re going to wire the brown lead to one set of terminals on your new capacitor and you’re going to wire the brown lead with the white tracer to the other set of terminals.

Using a single run capacitor with a three wire setup:

If you purchased a new single run capacitor and the condenser fan motor that you’re using only has three leads coming off of it, this will be the wiring setup that you’ll be using. You’re going to wire the black lead back to where it was previously wired. This will likely be back to your contactor. You’re going to wire the white lead to one set of terminals on your new capacitor. You’re going to need to wire a jumper from this set of terminals back to the other leg on your contactor. Finally, you’re going to wire the brown lead to the opposite set of terminals on your new run capacitor than the common lead.

Sum it all up:

There’s always a sense of fulfillment when completing a project yourself, but wiring a new condenser fan motor and run capacitor can be a bit tricky if you haven’t done it before. Safety is always the highest priority. Make sure the electrical supply to the condenser unit is disconnected before beginning any work. Use your multimeter to confirm the disconnection. If you’re not comfortable working with electricity, contact a local HVAC contractor and they will be more than happy to complete this task for you.

It’s very helpful to document the location of existing wire connections before removing the condenser fan motor or run capacitor. Use a camera to take pictures of the connections and reference the pictures when installing the new condenser fan motor and run capacitor.

For a visual picture of typical wiring configurations, reference the following guide: HVAC Condenser Fan Motor Wiring Diagram.

Finally, this guide is intended to be used as a general overview of common condenser unit wiring schematics. Some condenser fan motors wire to a circuit board while others use proprietary plugs for their connectors. We strongly recommend referring back to your unit’s manual for proper wiring instructions.

Let us Find Your Condenser Motor or Capacitor for You

 

Share this entry
  • Share on Facebook
  • Share on Twitter
  • Share on Linkedin
  • Share by Mail
12 replies
  1. lindquist
    lindquist says:
    May 26, 2018 at 11:33 pm

    I couⅼdn’t rеfrain from commenting. Well written!

    Reply
  2. Frederick Plutyk
    Frederick Plutyk says:
    July 18, 2018 at 1:45 pm

    Great information

    Reply
  3. Ray Lewis
    Ray Lewis says:
    July 26, 2018 at 11:28 pm

    Is there risk to hooking up the brown/white wire to a dual run capacitor? I just replaced the fan motor and capacitor, the original motor had 3 wires the new 4. The wiring diagram said to hook it up to the common lead on the capacitor. So I did. Will it cause ether fan to overspend and/or any damage? Do I remove it or is it safe to leave it.

    Reply
    • Craig Bagdon
      Craig Bagdon says:
      July 27, 2018 at 11:32 am

      Ray — Great question. On a dual run capacitor, there are 3 terminals. 1 labeled H or HERM of the compressor, one labeled C or COM for the common, and 1 labeled F or FAN for the fan motor.

      Since most OEM motors only have 3 wires and most replacement condenser fan motors have 4 wires, this creates a little confusion.

      The common lead (white) and the brown with the white tracer contractor leads are wired into the same circuit, so the brown with the white tracer can be cut off and insulated with a wire nut and electrical tape — you don’t need it.

      Simply wire the common lead (white) to the common terminal, the contractor lead (solid brown) to the F terminal, and whatever lead came from the compressor and you should be set.

      Reply
    • stephen nightingale
      stephen nightingale says:
      October 29, 2018 at 4:45 pm

      I would leave the brown/white lead alone. Either cable tie it safely or plug it on to a common on the dual run capacitor.

      Reason:
      when your dual run capacitor eventually gives out and you go to the store only to find they dont have any dual run caps available in your size but they do have two single caps to get you going again. That brown/white connector will be waiting to plug onto the fan cap common.
      Yes it happened to me.

      Reply
      • Craig Bagdon
        Craig Bagdon says:
        October 17, 2019 at 10:59 am

        Stephen –

        That’s a really great point. Down the road, if you’re put into a situation where you need to buy two run capacitors instead of a single dual run capacitor, having the brown w/ the white tracer lead will certainly help.

        – Craig

        Reply
  4. Roy rowley
    Roy rowley says:
    February 22, 2019 at 6:26 am

    How do I wire a ydk14 -4 using a separate capacitor on a evaporator

    Reply
  5. Chris Pratt
    Chris Pratt says:
    March 9, 2019 at 6:44 pm

    I have to agree with Lindquist. VERY well written!

    Reply
  6. Garry
    Garry says:
    June 25, 2019 at 4:51 pm

    That wiring diagram in the second to last paragraph was EXTREMELY helpful!

    Reply
    • Craig Bagdon
      Craig Bagdon says:
      October 17, 2019 at 10:59 am

      Garry –

      I’m happy to hear that it helped!

      – Craig Bagdon

      Reply
  7. Olivia Elliott
    Olivia Elliott says:
    October 16, 2019 at 7:49 pm

    What if the replaced fan condensor now has wires exposed at top. We just had new motor placed ( under warranty) . 412 dollars later for labor, out wires are not in air conditioner metal protector, they are outside the top of air conditioner?!? Is this a problem!? A squirrel or anything could get them!?

    Reply
    • Craig Bagdon
      Craig Bagdon says:
      October 17, 2019 at 8:55 am

      Olivia –

      Thank you very much for your comment. While there are differences among the various units and models, it’s common for the outdoor condenser units to be connected to the main electrical supply with a whip. The internal leads and wires are often harnessed together and protected from the elements by the condenser unit’s outer shell.

      – Craig Bagdon

      Reply

Trackbacks & Pingbacks

Leave a Reply

Want to join the discussion?
Feel free to contribute!

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Request a Quote

Post Categories

  • Aegis Shaft Grounding Rings
  • Bearings
  • Belts
  • Brushes
  • Company News
  • Condenser
  • CoolBlue
  • Cooling Season
  • DC Motors
  • Efficiency
  • Electric Motor Protection
  • Electric Motors
  • Fan Blades
  • Field Services
  • Heating Season
  • Infrared Inspection
  • Motor Repair
  • Motor Starters
  • News
  • Overload Relays
  • Predictive Maintenance
  • Reliability Services
  • Servo Motors
  • Uncategorized
  • Variable Frequency Drives

Dreisilker Information

  • About Dreisilker
  • Career Opportunities
  • Our Blog
  • Contact Us
  • Request a Quote

Quick Links

  • Branch Locations
  • Repair Services
  • Reliability and Field Services

STAY UP TO DATE –

Sign up for our newsletter:

 

How-To Get those AC’s Bumping with Ice-Cold Air Before the Heat Overwhelms... Aegis Shaft Grounding Rings Protect your Motors and Bearings
Scroll to top